Abstract
Water leakages in a water distribution system may vary from 5% to 55% of total supply and generally increase with pressure. The connection modeled by several studies as: qk leak = βklkPkak where P is the pressure in pipe k, 1 is the pipe length, and α, β are the leakage model coefficients. A method is proposed in this study for calibrating α, β. The pipes in the network are partitioned according to their properties, and for every group of pipes, the α, β values are searched. Through using a genetic algorithm and EPANET the values of α, β are modified until appropriate calibration matching is attained.
| Original language | English |
|---|---|
| Pages (from-to) | 664-671 |
| Number of pages | 8 |
| Journal | Procedia Engineering |
| Volume | 89 |
| DOIs | |
| State | Published - 2014 |